Category 6 U/FTP Outdoor Installation Cable
Cat. 6 U/FTP Outdoor Cable
Standards:
ANSI/TIA 568.2-D:2018
ISO/IEC 11801-1 Class E:2017
IEC61156-5:2012 (Edition 2.0)
CENELEC EN 50173-1:2018
CENELEC EN 50288-5-1:2011
RoHS compliant (EU Directive 2011/65/EC)
Application:
1000BASE-TX, 1000BASE-T and lower protocol
Campus backbone for CCTV System
Outside plant applications
Сonfiguration:
Conductor
Material
Bare Copper
Construction
23 AWG
Insulation
Material
PE
Diameter
1.35 ± 0.10mm
Pair shielding
Material
Individual Al/Pet foil (metal outside)
Drain Wire
Material/Size
Tinned Copper / 0,4 mm
Sheath
Material
UV-stabilized PE, thickness 0,6 mm
Size
Nominal diameter 6,85 mm
Electrical Performance
Dielectric Strength of Insulation
1200 V dc or 850 V ac / 2 seconds
Insulation Resistance Test
Min. 5000 MΩ/m
Conductor Resistance
Max.9.38 Ω/100m at 20℃
Resistance Unbalance
Max. 2%
Capacitance Unbalance
Max. 160 pF/100m
Mutual Capacitance
Max. 5600 pF/100m
Impedance
1~100MHz
100Ω ± 15%
100~250MHz
100Ω ± 22%
Attenuation & Near End Cross Talk
Frequency
Max. Attenuation
NEXT
PSNEXT
(MHz)
(dB/100 meters)
(dB), Min.
(dB), Min.
1MHz
2.0*
74.3*
72.3*
4MHz
3.8*
65.3*
63.3*
10MHz
6.0*
59.3*
57.3*
16MHz
7.6*
56.2*
54.2*
20MHz
8.5*
54.8*
52.8*
31.25MHz
10.7*
51.9*
49.9*
62.5MHz
15.4*
47.4*
45.4*
100MHz
19.8*
44.3*
42.3*
200MHz
29.0*
39.8*
37.8*
250MHz
32.8*
38.3*
36.3*
The asterisked (*) value are for information only. The minimum Next coupling loss for any pair combination at room temperature is to be greater than the value determined using the formula:
NEXT(f MHZ) ≧NEXT(0.772)-15LOG10(f MHZ/0.772)dB
Ordering information
Part No.
206646122
Description
Cat.6 U/FTP outdoor installation cable, PE, black
Packing
305m / reel
×
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it. Ok Privacy policy